Design of shunt active power filter to mitigate the harmonics caused by nonlinear loads

Application of non-linear electrical devices has led to a distortion in the output sine waveforms of source current and voltage. It may lead equipment (connected to it) to overheat and sometimes cause damage. This paper concentrates on the design and application of three-phase shunt active power fil...

詳細記述

書誌詳細
第一著者: Mohamed, Mohamed Asghaiyer
フォーマット: Dissertation
言語:英語
英語
英語
出版事項: 2015
主題:
オンライン・アクセス:http://eprints.uthm.edu.my/1355/
Abstract Abstract here
その他の書誌記述
要約:Application of non-linear electrical devices has led to a distortion in the output sine waveforms of source current and voltage. It may lead equipment (connected to it) to overheat and sometimes cause damage. This paper concentrates on the design and application of three-phase shunt active power filter (SAPF) by using p-q theory to mitigate the harmonics which are created by nonlinear loads. To obtain result for this paper, the MATLAB / Simulink was used as a simulation tool. The achieved results are within the recommended IEEE-519 standard i.e. less than 5% and also the power factor (PF) of the system to almost unity.